Description
T3SK7516V TROVE3SH3/16DR/ULX/FUSE/220V
Altronix T3SK7516V kit consists of Trove3 enclosure and TSH3 Software House/Altronix
backplane with 24VDC @ 10A and 12VDC @ 10A power supply/chargers, two (2) eight (8) fuse protected output access control module and eight (8) fuse protected output power distribution module. This kit also accommodates various combinations of Software House boards for up to sixteen (16) doors in a single enclosure. Trove simplifies board layout and wire management, reduces installation time and labor costs.
AL1024XB2V Power Supply/Charger - 1
Input
Voltage: 220VAC (working range 198VAC-256VAC), 50/60Hz, 2.5A.
Fusing: 5A / 250V.
Output
Voltage: 24VDC.
Current: 10A @ 24VDC continuous max.
Other: Overvoltage protection. Filtered and regulated.
AL1012XB220 Power Supply/Charger - 2
Input
Voltage: 220VAC (working range 198VAC-256VAC), 50/60Hz, 1.3A.
Fusing: 5A / 250V.
Output
Voltage: 12VDC.
Current: 10A @ 12VDC continuous max.
Other: Overvoltage protection. Filtered and regulated.
Both Power Supplies
Battery Charging:
Capacity: 12AH/12VDC (2 within enclosure) 40AH/65AH (requires separate enclosure).
Type: Sealed lead acid or gel type.
Failover: Upon AC loss, instantaneous.
(Batteries are sold separately).
Supervision
AC Failure: Form “C” contacts.
Battery: Form “C” contacts.
Indicators LED
Input: 220VAC is present.
DC Output: Powered.
Battery: Discharged or not connected.
PD8UL Power Distribution Module
Input
Voltage: 12VDC from AL1012XB220.
Outputs
Voltage: 12VDC.
Output Fuses: 3.5A/250V.
Indicators (LED)
Green LED: DC Output.
Two (2) ACM8 Access Power Controllers
Input
Voltage: 24VDC from AL1024XB2V.
Main Fuse: 10A / 250V.
Outputs
Voltage: 24VDC.
Eight (8) 24VDC independently controlled fused outputs:
a) Fail-Safe and/or Fail-Secure power outputs. Form “C” Relays rated 28VAC or VDC @ 2.5A.
b) Auxiliary power outputs (unswitched).
c) Any combination of the above.
Output Fuses: 3.5A / 250V.
Indicators (LED)
Red LEDs: Outputs are triggered (relays energized).
Green LED: FACP disconnect is triggered.
Environmental
Temperature
Operating: 0° C to 49° C (32° F to 120° F).
Storage: - 20° C to 70° C ( - 4° F to 158° F).
Relative Humidity
Relative Humidity: 85% +/- 5%.
BTU/Hr. (approx.):
217 BTU/Hr.