Description
T3M75XK1D T3MK75F16SD/PWX/KIT1
Altronix T3M75XK1D is a 16-door access and power integration kit which includes Altronix
power and sub-assemblies along with factory installed wire management and wire assemblies that are pre-configured with terminal blocks for Mercury hardware. This unit provides ample power and dual voltage outputs to support Mercury platform controllers and locking devices. The T3M75XK1D accommodates one (1) Intelligent Dual Reader Controller and seven (7) Dual Reader Interface Modules. Trove Plus simplifies field installations and provides reliable, robust critical power and control for the most demanding applications.
*Also compatible with these authentic Mercury partners:
AccessNsite, Avigilon, BadgePass, BluBox, Feenics, Genetec, Identicard, IMRON, Johnson Controls, Kastle, Keri Systems, LockState, Maxxess, Midpoint Security, NLSS, Open Options, Panasonic i-PRO MonitorCast, Quintron, RS2, S2 Security, Schneider Electric, Vanderbilt
eFlow104NB Power Supply/Charger - 1
Input
Voltage: 120VAC, 60Hz, 4.5A.
Main Fuse: 6.3A / 250V.
Output
Voltage: 24VDC @ 10A.
Auxiliary: 1A (unswitched).
Protection: Overvoltage protection. Filtered and regulated.
eFlow102NB Power Supply/Charger - 2
Input
Voltage: 120VAC, 60Hz, 3.5A.
Main Fuse: 5A / 250V.
Output
Voltage: 12VDC @ 10A.
Auxiliary: 1A (unswitched).
Protection: Overvoltage protection. Filtered and regulated.
Both Power Supplies
Battery Charging
Capacity: 12VDC/12AH (4 within enclosure); 40AH/65AH (requires separate enclosure)
Type: Sealed lead acid or gel type
Failover: Upon AC loss, instantaneous
(Batteries are sold separately).
Fire Alarm Disconnect
Supervised: Latching or non-latching.
EOL: 10K Resistor.
Supervision
AC Failure: Form “C” contacts.
Battery: Form “C” contacts.
Low DC Power Shutdown: Shuts down DC output terminals if battery voltage drops below 71-73% for 12V units and 70-75% for 24V units (depending on the power supply). Prevents deep battery discharge.
Indicators LED
AC Input: 120VAC is present.
DC Output: Powered.
Battery: Discharged or not connected.
Two (2) PDS8CB Dual Input Power Distribution Modules
Input
Voltage: 24VDC from eFlow104NB and 12VDC from eFlow102NB.
Input PTC: 9A.
Outputs
Voltage: 12VDC and/or 24VDC.
Any of the eight (8) power outputs are selectable to follow power Input 1 or Input 2.
Individual outputs may be set to OFF position for servicing.
Outputs Ratings
PTCs: 2.5A.
Indicators (LED)
DC Output: Eight (8) individual output LEDs.
Green: 12VDC
Red: 24VDC.
Two (2) ACMS8CB Dual Input Access Power Controllers
Input
Voltage: 24VDC from eFlow104NB and 12VDC from eFlow102NB.
Input PTC: 9A.
Outputs
Voltage: 12VDC or 24VDC individually selectable.
Eight (8) selectable 12VDC - 24VDC independently controlled outputs or eight (8) independently controlled Form “C” relay outputs:
a) Fail-Safe and/or Fail-Secure power outputs. Form “C” Relays rated 28VAC or VDC @ 2.5A Rated.
b) Auxiliary power outputs (unswitched).
c) Any combination of the above.
Any of the eight (8) PTC protected power outputs are selectable to follow power Input 1 or Input 2.
Individual outputs may be set to OFF position for servicing.
Outputs Ratings
PTCs: 2.5A.
Indicators (LED)
Red LEDs: Outputs are triggered (relays energized).
Blue LED: FACP disconnect is triggered.
Individual voltage LEDs:
Green: 12VDC
Red: 24VDC
Environmental
Temperature
Operating: 0° C to 49° C (32° F to 120° F).
Storage: - 20° C to 70° C ( - 4° F to 158° F).
Relative Humidity
Relative Humidity: 85% +/- 5%.
BTU/Hr. (approx.):