Description
T2PHK3316 ALTX/OPENPATH 16DR/ULX/FUSE
Altronix T2PHK3316 kit consists of Trove2 enclosure, TCV2 Openpath/Altronix backplane with two (2) 12 or 24VDC @ 6A power supply/chargers, and two eight (8) fuse protected output access control modules. This kit also accommodates up to two (2) Openpath Core, two (2) Elevator Board, two (2) 4-Port or 8-Port modules for up to sixteen (16) doors in a single enclosure. Trove simplifies board layout and wire management, reduces installation time and labor costs.
Two (2) AL600ULXB Power Supply/Chargers
Input
Voltage: 115VAC, 60Hz, 3.5A max.
Fusing: 5A / 250V.
Outputs
Voltage: 12VDC or 24VDC selectable.
Current: 6A @ 12VDC or 24VDC continuous max.
Other: Overvoltage protection. Filtered and regulated.
Battery Charging
Capacity: 12VDC/12AH (2 within enclosure); 40 AH / 65 AH (requires separate enclosure)
Type: Sealed lead acid or gel type
Failover: Upon AC loss, instantaneous
(Batteries are sold separately).
Supervision
AC Failure: Form “C” contacts.
Battery: Form “C” contacts.
Indicators LED
Input: 115VAC is present.
DC Output: Powered.
Battery: Discharged or not connected.
Two (2) ACM8 Access Power Controllers
Input
Voltage: 24VDC from AL600ULXB.
Input Fuse: 10A / 250V.
Outputs
Voltage: 24VDC.
Eight (8) 24VDC independently controlled fused outputs:
a) Fail-Safe and/or Fail-Secure power outputs. Form “C” Relays rated 28VAC or VDC @ 2.5A.
b) Auxiliary power outputs (unswitched).
c) Any combination of the above.
Output Fuses: 3.5A/250V.
Indicators (LED's)
Red LEDs: Outputs are triggered (relays energized).
Green LED: FACP disconnect is triggered.
Environmental
Temperature
Operating: 0° C to 49° C (32° F to 120° F).
Storage: - 20° C to 70° C ( - 4° F to 158° F).
Relative Humidity
Relative Humidity 85% +/- 5%.
BTU/Hr. (approx.):
12VDC: 74 BTU/Hr.
24VDC: 148 BTU/Hr.
12VDC and 24VDC: 111 BTU/Hr.