Description
Altronix EFLOW104NK1 24VDC@10A&12VDC@6A, FAI, 115
Altronix eFlow104NK1 sub-assembly kit converts a 120VAC, 60Hz input into one (1) 5VDC or 12VDC selectable output at up to 6A supply current and one (1) 24VDC output. It also offers a suite of features that includes fire alarm disconnect, overvoltage protection, and low power disconnect which prevents deep discharge of stand-by batteries.
Input
120VAC, 60Hz, 4.5A.
Input fuse: 6.3A/250V.
Output
Two outputs:
- Selectable 5VDC or 12VDC output;
- 24VDC output.
5VDC @ 6A continuous and 24VDC @ 8A continuous or 12VDC @ 6A continuous and 24VDC @ 6A continuous
Auxiliary Class 2 power-limited output rated @ 1A (unswitched).
Overvoltage protection.
Battery Charging
Built-in charger for sealed lead acid or gel type batteries.
Maximum charge current 1.0A.
Automatic switch over to stand-by battery when AC fails. Transfer to stand-by battery power is instantaneous with no interruption.
Transfer to stand-by battery power is instantaneous with no interruption.
(Batteries are sold separately).
Supervision
Low power shutdown. Shuts down DC output terminals if battery voltage drops below 71-73% for 12V units and 70-75% for 24V units (depending on the power supply). Prevents deep battery discharge.
Fire Alarm Disconnect
Supervised Fire Alarm disconnect (latching or non-latching) 10K EOL resistor. Operates on a normally open (NO) or normally closed (NC) trigger.
AC fail supervision (form “C” contacts).
Battery fail & presence supervision (form “C” contacts).
Electrical
Temperature:
Operating: 0° C to 49° C (32° F to 120° F).
Storage: - 20° C to 70° C ( - 4° F to 158° F).
Relative Humidity: 85% +/- 5%.
BTU/Hr. (approx.): 123 BTU/Hr.
Visual Indicators
Green AC Power LED indicates 120VAC present.
AC input and DC output LED indicators.
Additional Features
Short circuit and overload protection.
Unit is complete with power supply, enclosure, battery leads and cam lock.