Description
Altronix COMMBATT1 POWER FOR ARCS/ERCES SYSTEMS
Altronix CommBatt1 is an in-building power and battery backup solution for emergency
response radio coverage system. Designed and engineered to meet NFPA 1225 codes
providing integrators and consultants with a BDA power and backup option.
Input
Voltage: 115VAC-220VAC 50/60Hz, 2A
Input Fuse: 5A/250V
Outputs
Voltage: 12VDC or 24VDC
Current
UL2524 Specifications:
24V @ 5.5A total or 12V @ 9A total current
UL864/ULC-S527 Specifications:
24V: 3.5A standby, 6A alarm
12V: 3.5A standby, 12A alarm
Auxiliary:
Power-limited @ 0.6A (unswitched)
Other:
Overvoltage protection. Filtered and regulated
Battery Charging
Type: Sealed lead acid or gel type; Two (2) 55AH batteries in series for 24V, One (1) or two (2) in parallel for 12V, 12AH option for UL864
Charge Current: 3A for 12V and 2A for 24V
Fuse Rating: 20A/32V
(Batteries are sold separately).
Supervision (Form “C” Contacts)
AC: Failure/Brownout
Battery: Low Battery/Battery Presence/Battery fail
Component Trouble: Critical Component Failure
Charger Circuit Failure
FACP Reporting
Indicators
Component Failure: Critical Component Failure
Battery: Low or missing battery
AC Input: AC Brownout or failure
Charger: Charger trouble
Heartbeat: Processor failure
Critical Failure: Wrong voltage, shutdown indicator
Physical and Environmental
NEMA-4, UL Listed aluminum red powder coated wall mount enclosure with IP 65 battery vent and locking door, IP-68 cable entries
Temperature
Operating: 0ºC to 49ºC (32ºF to 120ºF)
Storage: – 20ºC to 70ºC (– 4ºF to 158ºF)
Relative Humidity
85% +/– 5%
BTU/Hr. (approx.)
74 BTU/Hr.